UPS
|
Features:
100% digital technology
Self-diagnosis, circuit control, parameters
setting and program management are based on
3 high speed microcontrollers.
Applies high-tech components
DDC (Direct Digital Control), DSP (Digital
Signal Processing), ASIC (Application Specific
IC) and CPU are used in this
system.
Super performance from
IGBT
High speed on/off, operating on high voltage
and large current, simple gate control circuits
(voltage-controlled), high
efficiency, and high stability.
Fully meets sharp load fluctuation from 0
to 100%
Completely meet the requirements of sharp
load fluctuation without transferring to bypass,
and maintain the output
within tolerance
Large screen LCD display
Users can conveniently operate the UPS according
to the instructions and easily get UPS operating
status at any time
via large screen LCD.
Perfect protections
Built-in over/low-voltage, over-current, overload,
and short circuit protections ensure lowest
failure rate.
Low output voltage distortion
Owing to partial circulating current control,
inverter could rapidly control impulse current
from load change and surge.
UPS can quickly respond to load change via
feedback control.
Intelligent battery
management
UPS will automatically charge and discharge
the battery in float charging or boost charging
mode according to the cycle
set by the internal software, and automatically
maintain the battery without manual operation,
which prolongs the battery
life.
| Model |
EA8610 |
EA8615 |
EA8620 |
EA8630 |
EA8640 |
EA8650 |
EA8660 |
EA8680 |
| VA Rating |
10KVA |
15KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
| Operating
Mode and Principle |
| True on-Line,
Static Bypass(Uninterruptible Switch),
Dual Conversion, Input & Output Galvanic
Isolation |
| AC Input |
| Phase |
3 Phases
+ N + G |
| Voltage |
380V ± 25% |
| Frequency |
50/60Hz ±
5% |
| Soft Start |
0~100% 5s |
| Bypass
Input |
| Phase |
Single Phase |
| Voltage |
220V ± 20% |
| Frequency |
50/60Hz ±
5% |
| Transfer Time |
0ms, Inverter
to Bypass (Overload) |
| DC
System |
| DC Voltage |
360V (Rated
Voltage) 30pcs Batteries |
| 315V (Shutdown
Voltage) |
| Current |
25A |
38A |
51A |
76A |
101A |
126A |
152A |
203A |
| AC
Output |
| Phase |
Single Phase |
| Voltage |
220V ± 1%(Stable
Load); 220V ± 5%(Fluctuated Load) |
| Frequency |
50~60Hz ±
0.05% (Battery Mode) |
| Power Factor |
0.8 |
| Waveform |
True Sine
Wave |
| Harmonic Distortion |
<3%(Linear
Load); <5%(Non-Linear Load) |
| Dynamic |
Instantaneously
Changing of Load (0 to 100%), changing
of Output Voltage < 5% |
| Time |
Transient
Recovery Time < 10ms |
| Overload |
125% for
1Min; 150% for 1s |
| Cooling |
Forced Wind |
| System |
| Efficiency |
91% |
91% |
92% |
93% |
93% |
93% |
93% |
95% |
| Communication |
RS232 or
SNMP |
| Temperature |
0~40. (Operating) |
| Humidity |
30~90% |
| Noise(db) |
48-60 |
53-65 |
55-65 |
| Dimension(mm) |
685×350×930 |
770×430×1080 |
750×720×1450 |
750×860×1600 |
| VA Rating |
500 VA |
600 VA |
650 VA |
1000 VA |
1200 VA |
1500 VA |
2000 VA |
| Real Power Rating |
300 W |
360 W |
390 W |
480 W |
800 W |
820 W |
1200 W |
| Operating
Mode and Principle |
| True on-Line,
Static Bypass(Uninterruptible Switch),
Dual Conversion, Input & Output Galvanic
Isolation |
| AC
Input |
| Phase |
3 Phases
+ N + G |
| Voltage |
110V/220V
± 25% |
| Frequency |
45-55±1Hz/55~65±1Hz |
| Soft Start |
0~100% 5s |
| Bypass
Input |
| Phase |
Single Phase |
| Voltage |
220V ± 20% |
| Frequency |
50/60Hz ±
5% |
| Transfer Time |
0ms, Inverter
to Bypass (Overload) |
| DC
System |
| DC Voltage |
360V (Rated
Voltage) 30pcs Batteries |
| 315V (Shutdown
Voltage) |
| Current |
25A |
38A |
51A |
76A |
101A |
126A |
152A |
203A |
| AC
Output |
| Phase |
Single Phase |
| Voltage |
110V/220V
± 10% |
| Frequency |
AC Mode:
Track the Utility, Battery Mode: 50±0.5Hz/60±0.5Hz |
| Power Factor |
0.8 |
| Waveform |
True Sine
Wave |
| Harmonic Distortion |
<3%(Linear
Load); <5%(Non-Linear Load) |
| Dynamic |
Instantaneously
Changing of Load (0 to 100%), changing
of Output Voltage < 5% |
| Time |
Transient
Recovery Time < 10ms |
| Overload |
125% for
1Min; 150% for 1s |
| Cooling |
Forced Wind |
| System |
| Efficiency |
91% |
91% |
92% |
93% |
93% |
93% |
93% |
95% |
| Communication |
RS232 or
SNMP |
| Temperature |
0~40. (Operating) |
| Humidity |
30~90% |
| Noise(db) |
48-60 |
53-65 |
55-65 |
| Dimension(mm) |
685×350×930 |
770×430×1080 |
750×720×1450 |
750×860×1600 |
Amigo
UPS Prices :
1. Amigo 650 VA - 3,000
2. Amigo 1200 VA -5,500
|
|